sdf

ECO SMART – HYPER INVERTER ( R410A ) – COOLING ONLY

 

MODEL Unit SRK10YL-S SRK13YL-S SRK18YL-S SRK24YRV-S6
Indoor Unit SRK10YL-S SRK13YL-S SRK18YL-S SRK24YRV-S6
Outdoor Unit SRC10YL-S SRC13YL-S SRC18YL-S SRC24YRV-S6
Maximum Tonnage** 0.80 1.1 1.6 2.2
BEE STAR RATING – 2019 5 Star 5 Star 4 Star 5 Star
Compressor Type Super Tropical – DC PAM Inverter – Return Cooled – Rotary Twin Rotary
VFD – Variable Frequency Drive Inverter Vector Control Technology for Higher Efficiency
Minimum Compressor RPM 7 ~ 15 RPM – Using Vector Control Technology
Refrigerant Volume Control Using Motorized Electronic Expansion Valve for Variable Refrigerant Flow
LCD Remote Control (iPM Controller) iPM ( Intelligent Power Module )
Power Source 1 Phase, 220 / 230 V, 50 Hz
Maximum Cooling Capacity at** 120% Load BTU/hr 9861 13252 19609 26815
Rated Cooling Capacity at 100% Load 9247 12454 18425 25198
Rated Cooling Capacity at 50%  Load 5203 6995 9646 13460
Maximum Cooling Capacity at** 120% Load Watts 2890 3884 5747 7859
Rated Cooling Capacity at 100% Load 2710 3650 5400 7385
Rated Cooling Capacity at 50%  Load 1525 2050 2827 3945
Rated Power Consumption at 100% Load watts 670 975 1560 2000
Rated Power Consumption at 50%  Load 253 369 582 772
Rated EER / COP at 100% Load W/w 4.3 3.7 3.5 3.7
Rated EER / COP at 50%  Load 6.0 5.6 4.9 5.1
Rated Indian Seasonal Energy Efficiency ISEER 5.41 5.00 4.49 4.75
Current ( Minimum ~ Maximum )** A 0.5 ~ 3.0 0.65 ~ 4.3 0.87 ~ 7.0 1.52 ~ 9.0
Dimension (H x W x D) Indoor Unit mm 268 x 790 x 224 268 x 790 x 224 268 x 790 x 224 339 x 1197 x 262
Outdoor Unit mm 540 x 780(+62) x 290 540 x 780(+62) x 290 595 x 780(+62) x 290 750 x 880(+88) x 340
Weight Indoor Unit Kgs 9.0 9.0 10.0 18.5
Outdoor Unit Kgs 29 32 35 61
Cooling Coil Row Indoor Unit No.s 2 3 3 3
Air Flow (CMH) Indoor Unit m3/hr 600 790 1000 1450
Long Reach Air Flow Upto Indoor Unit Meters 4.57 4.57 5.18 18.28
Self Diagnosis Function Indoor Unit Yes Yes Yes Yes
Sound Level (H/M/L) Indoor Unit dB 39 / 30 / 22 39 / 30 / 22 45 / 38 / 26 41/38/34/25(Silent
Mode)
Louver Swing Indoor Unit 3D + 3D AUTO
Special Filter Indoor Unit Enzyme + Solar + Anti Bacterial
Fan Indoor Unit Anti – Micro Bial Fan
DC Fan Motor Speed Indoor Unit Auto / Powerful / High / Medium / Low / Dry/ (Ultra Low-in-silent mode in SRK24YRV- S6)
Refrigerant R410A
Refrigerant Injection in Coil 4 Point – Multi Port
Refrigerant Piping Liquid Line mm 6.35 ( 1/4″ )
Thickness:18Gauge(1mm) Gas Line mm 9.52 ( 3/8″ ) 9.52 ( 3/8″ ) 12.7 ( 1/2″ ) 15.88 ( 5/8″ )
Main Power Supply to Outdoor Unit 2.5 mm2 x 3 cores (including Earthing)
Connecting wiring B/w IDU & ODU 2.5 mm2 x 4 cores (including Earthing)
Area Coverage *** Sq.Meters 7.43 ~ 13.00 12.07 ~ 15.79 13.93 ~ 18.58 23.22 ~ 41.80

5 Replies to “sdf”

Leave a Reply

Your email address will not be published. Required fields are marked *